| Product number | JUT1-6 | JUT1-6PE | JUT1-6S |
| Product type | Rail Terminals | Rail ground terminal | Test rail terminal block |
| Mechanical structure | screw type | screw type | screw type |
| layers | 1 | 1 | 1 |
| Electric Potential | 1 | 1 | 1 |
| connection volume | 2 | 2 | 2 |
| Rated cross section | 6 mm2 | 6 mm2 | 6mm2 |
| Rated current | 41A | 41A | |
| Rated voltage | 800V | 400V | |
| open side panel | yes | no | no |
| grounding feet | no | yes | no |
| other | when connecting the open housing side of modular screw rail grounding terminals of the same series and size, the terminal must be equipped with a cover if the insulation voltage is expected to be higher than 320 V. | For fuse size G/5x20 | |
| Application field | electricity, mechanical engineering, factory engineering, process industry, etc. | ||
| color | gray, customizable | yellow and green | black, customizable |
| line contact | |||
| Stripping length | 10mm | 10mm | 13mm |
| Rigid Conductor Cross Section | 0.2mm² — 10mm² | 0.2mm² — 10mm² | 0.5mm² — 10mm² |
| Flexible conductor cross section | 0.2mm² — 6mm² | 0.2mm² — 6mm² | 0.2mm² — 6mm² |
| Rigid Conductor Cross Section AWG | 24-8 | 24-8 | 20-8 |
| Flexible Conductor Cross Section AWG | 24-12 | 24-10 | 20-10 |
| thickness | 8.2mm | 8.2mm | 8.2mm |
| width | 42.5mm | 42.5mm | 72mm |
| high | |||
| NS35/7.5 high | 47mm | 47mm | 51.5mm |
| NS35/15 high | 54.5mm | 54.5mm | 59mm |
| NS15/5.5 high |
| Flame retardant grade, in line with UL94 | V0 | V0 | V0 |
| Insulation Materials | PA | PA | PA |
| Insulation material group | I | I | I |
| standard test | IEC 60947-7-1 | IEC 60947-7-2 | IEC 60947-7-1 |
| Rated voltage(III/3) | 800V | 400V | |
| Rated current(III/3) | 41A | 41A | |
| Rated surge voltage | 8kv | 8kv | 6kv |
| Overvoltage class | III | III | III |
| pollution level | 3 | 3 | 3 |
| Surge Voltage Test Results | -60 °C — 105 °C (Maximum short-term operating temperature, electrical characteristics are relative to temperature.) | -60 °C — 105 °C (Maximum short-term operating temperature, electrical characteristics are relative to temperature.) | -40 °C — 105 °C (Maximum short-term operating temperature, electrical characteristics are relative to temperature.) |
| Ambient temperature (storage/transport) | -25 °C — 60 °C (short term (up to 24 hours), -60 °C to +70 °C) | -25 °C — 60 °C (short term (up to 24 hours), -60 °C to +70 °C) | -5 °C — 70 °C (short term (up to 24 hours), -60 °C to +70 °C) |
| Ambient temperature (assembled) | -5 °C — 70 °C | -5 °C — 70 °C | -5 °C — 70 °C |
| Ambient temperature (execution) | -5 °C — 70 °C | -5 °C — 70 °C | -5 °C — 70 °C |
| Relative Humidity (Storage/Transportation) | 30 % — 70 % | 30 % — 70 % | 25 % — 75 % |
| RoHS | No excessive harmful substances | No excessive harmful substances | No excessive harmful substances |
| Connections are standard | IEC 60947-7-1 | IEC 60947-7-2 | IEC 60947-7-1 |
| Surge Voltage Test Results | Passed the test | Passed the test | Passed the test |
| Power frequency withstand voltage test results | Passed the test | Passed the test | Passed the test |
| Temperature rise test results | Passed the test | Passed the test | Passed the test |